HomeProductsArrowArrowArrowCHA/Y/A 1302÷6002 - MaxiPower
Back Back

CHA/Y/A 1302÷6002 - MaxiPower

Klima-Therm by Clint
Find out more about the brand

Air conditioning configurator

close
Air conditioning configurator

Air cooled chillers with energy efficiency class A.

 

Chillers with energy efficiency class A, operating on R134a refrigerant and fitted with the Microchannel heat exchanger (optional), are designed for office and industrial air conditioning and heating systems.

  • Screw Inverter compressors (optional)
  • 2-year warranty
  • Energy efficiency class A
  • MultiPower technology
  • Microchannel heat exchanger (optional)

 

Chilled water systems – Inverter – Heat pump – Class A – Microchannel coil (option) – R134a refrigerant
See the most important functions
R134a refrigerant
R134a refrigerant
Class A
Class A
Scroll inverter compressors
Scroll inverter compressors
Scroll compressors
Scroll compressors
Axial fans
Axial fans
Cooling - heating version
Cooling - heating version
Cooling only version
Cooling only version
Shell & Tube exchanger
Shell & Tube exchanger
Microchannel coil
Microchannel coil
R513A refrigerant
R513A refrigerant
R134a refrigerant
R134a refrigerant
R134a refrigerant

Units with the refrigeration system containing R134a (GWP 1430) refrigerant.

Class A
Class A
Class A

Units with high energy efficiency confirmed by the EER and ESEER ratios in class A.

Scroll inverter compressors
Scroll inverter compressors
Scroll inverter compressors

Semi-hermetic single-screw satellite compressors. With integrated oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, hot gas shut-off valves and stepless capacity control.

Scroll compressors
Scroll compressors
Scroll compressors

Semi-hermetic single-screw satellite compressors. With integrated oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, and hot gas shut-off valves.

Axial fans
Axial fans
Axial fans

Axial fans directly coupled to a three phase electric motor and external rotor, equipped with a grille protecting the fan located at the air outlet.

Cooling - heating version
Cooling - heating version
Cooling - heating version

Units in the cooling/heating version operate using the heat pump function. They can cool or heat water, chilled water or air.

Cooling only version
Cooling only version
Cooling only version

The units in the cooling-only version provide the basic function of cooling water, chilled water or air, while other functions are optional.

Shell & Tube exchanger
Shell & Tube exchanger
Shell & Tube exchanger

Shell and tube heat exchanger with two independent cooling circuits and one water circuit.

Microchannel coil
Microchannel coil
Microchannel coil

Condenser with two Microchannel coils, made entirely of aluminium.

R513A refrigerant
R513A refrigerant
R513A refrigerant

Units with the refrigeration system containing R513A (GWP 631) refrigerant.

Technical specifications

Model

 

 

EER

COP

 

Capacity

C/G

kW

Absorbed power

C/G

kW

Electric power supply

V/pH/Hz

 

Dimensions

mm

 

Weight

kg

 

Refrigerant charge

kg (CO2eq-T)

 

CHA/Y/A 1302 3,2 263 82 400/3/50 4400/2200/2100 3562 2x31(2x44,330)
3,4 272 81 5550/2200/2100 4172 2x33(2x47,190)
CHA/Y/A 1502 3,3 313 96 400/3/50 4400/2200/2100 3609 2x33(2x47,190)
3,4 324 95 5550/2200/2100 4219 2x34(2x48,620)
CHA/Y/A 1702 3,2 359 114 400/3/50 5000/2200/2100 3708 2x34(2x48,620)
3,3 372 113 5550/2200/2100 4578 2x37(2x52,910)
CHA/Y/A 1902 3,2 413 131 400/3/50 5550/2200/2100 4207 2x43(2x61,490)
3,3 428 130 7750/2200/2100 4987 2x46(2x65,780)
CHA/Y/A 2002 3,2 464 146 400/3/50 6200/2200/2100 4782 2x44(2x62,920)
3,3 480 144 7750/2200/2100 5502 2x49(2x70,07)
CHA/Y/A 2602 3,2 574 179 400/3/50 6700/2200/2100 5202 2x67(2x95,810)
3,4 594 177 8900/2200/2100 6372 2x73(2x104,390)
CHA/Y/A 3002 3,2 696 219 400/3/50 8900/2200/2100 6496 2x85(2x121,550)
3,3 721 217 10050/2200/2100 7586 2x89(2x127,270)
CHA/Y/A 3602 3,3 839 256 400/3/50 11100/2200/2100 7430 2x116(2x165,88)
3,4 869 253 13400/2200/2100 8500 2x111(2x158,73)
CHA/Y/A 4202 3,1 959 305 400/3/50 11100/2200/2100 7484 2x116(2x165,88)
3,3 993 302 13400/2200/2100 8984 2x121(2x173,03)
CHA/Y/A 4802 3,2 1136 352 400/3/50 11100/2200/2500 8773 2x141(2x201,63)
3,4 1176 348 13400/2200/2500 10403 2x148(2x211,64)
CHA/Y/A 5002 3,3 1264 380 400/3/50 13400/2200/2500 9640 2x171(2x244,53)
CHA/Y/A 5402 3,2 1398 440 400/3/50 13400/2200/2500 10380 2x173(2x247,39)
CHA/Y/A 6002 3,2 1533 480 400/3/50 13400/2200/2500 10800 2x200(2x286,00)

 

Technical data refer to selected models from the Klima-Therm offer. The manufacturer is constantly improving its products – to verify the data, please contact an Authorized Dealer. C-Cooling, H-Heating; Cooling capacity- Chilled water from 12 to 7 °C, ambient temperature 35°C; Heating capacity-Heating water from 40 to 45 °C ambient air temperature 7 °C d.b./6 °C w.b..

Cooling only models 1302÷1702 are compliant to the ErP 2021 Regulation. Cooling only models 1902÷6002 are compliant to the ErP 2021 Regulation for process cooling application; for comfort cooling application they are compliant with EC or ECH accessory (EC Inverter fans).
Heat pump models 1302÷2002 are compliant to the ErP Regulation; models 2602÷6002 are compliant if provided with EC or ECH accessory (EC Inverter fans).