The XOC line of precision air conditioners is the most advanced solution for technological applications in facilities such as: server farms, power amplifier rooms of UMTS and GSM transmitters, NOCs (Network Operations Centre), cooling of computer racks, control rooms, power supply devices, and practically anywhere where heat loads are extremely high. XIP direct evaporation units with a dedicated remote condenser are suitable for operation with the XT Line series at outdoor temperatures of up to 52?C.

 

The operating principle: room air is treated in an evaporator through which the refrigerant flows; the condensation heat is discharged to an external air cooled condenser.

  • Innovative design
  • Compact units
  • Centrifugal fans
  • Scroll compressor
  • Simple maintenance
  • Low noise operation
AIRCOOLED DIRECT EXPANSION UNITS (R410A) with radial fans
Technical specifications

Model

 

EER

 

Wydajność

Chłodnicza

kW

Pobór mocy

kW

Zasilanie

V/Ph/Hz

Wymiary

HxWxD

Masa

kg

1009

3,00

9,2

3,1

 

230 / 1 / 50

1980x675x675

248

1011

2,99

11,5

3,9

1980x675x675

255

1015

3,31

15,5

4,7

 

 

 

 

 

 

 

 

 

 

400/3+N/50

1980x675x675

264

1020

3,14

19,9

6,3

1980x675x675

267

1025

3,05

24,4

8,0

1980x875x675

309

1030

3,19

30,0

9,4

1980x875x675

325

1040

2,84

40,4

14,2

1980x1350x890

507

1070

2,99

70,2

23,5

1980x1750x890

660

2035

2,67

35,3

13,2

1980x1350x890

511

2048

3,03

48,2

15,9

1980x1350x890

526

2055

3,23

54,9

17,0

1980x1350x890

560

2065

2,87

65,4

22,8

1980x1750x890

640

2080

2,95

79,1

26,8

1980x1750x890

698

2090

2,87

90,2

31,4

1980x2225x890

814

2100

2,92

101,0

34,6

1980x2225x890

841

2140

3,29

141,0

42,8

1980x2625x890

1031

4110

3,19

111,0

34,8

1980x2625x890

1031

4120

3,17

120,0

37,8

1980x2625x890

1058

4130

3,21

131,0

40,8

1980x2625x890

1056

 

Temperatura otoczenia 24 °C - R.H. 50%; Temperatura skraplania 45 °C.

Temperatura wody 7°C / 12°C

Ciśnienie dźwięku mierzone w wolnej przestrzeni, w odległości 2 m od urządzenia (ISO 3744), z kanałami podłączonymi na wylocie i wlocie powietrza (z wyjątkiem wlotu w wersji z wlotem OD GÓRY).