The WOP line of precision air conditioners is the most advanced solution for technological applications in facilities such as: server farms, power amplifier rooms of UMTS and GSM transmitters, NOCs (Network Operations Centre), cooling of computer racks, control rooms, power supply devices, and practically anywhere where heat loads are extremely high.

 

These units are characterised by the use of a water cooler as the primary and only heat exchanger.

  • Innovative design
  • Compact units
  • Chilled water
  • Simple maintenance
  • Low noise operation
CHILLED WATER UNITS with radial fans
Technical specifications

Model

 

Wydajność

Chłodnicza

kW

Pobór mocy

kW

Zasilanie

V/Ph/Hz

Wymiary

HxWxD

Masa

kg

0009

8,6

0,9

 

230 / 1 / 50

1980x675x675

209

0013

13,1

1,0

1980x675x675

217

0018

17,6

1,6

 

 

 

 

 

 

 

 

 

 

400/3+N/50

1980x675x675

222

0022

21,7

1,6

1980x675x675

228

0027

27,5

2,4

1980x875x675

273

0031

31,4

2,4

1980x875x675

278

0036

35,9

5,0

1980x1350x890

415

0048

47,7

5,0

1980x1350x890

425

0057

56,6

5,0

1980x1350x890

435

0063

63,4

5,0

1980x1350x890

446

0069

69,3

5,0

1980x1350x890

458

0079

79,1

7,6

1980x1750x890

520

0089

88,9

7,6

1980x1750x890

534

0097

96,8

7,6

1980x2225x890

550

0104

104

10,6

1980x2225x890

635

0117

117

10,6

1980x2625x890

655

0128

128

10,6

1980x2625x890

673

0142

142

10,1

1980x2625x890

781

0155

155

10,1

1980x2625x890

802

 

Temperatura otoczenia 24 °C - R.H. 50%; Temperatura skraplania 45 °C.

Temperatura wody 7°C / 12°C

Ciśnienie dźwięku mierzone w wolnej przestrzeni, w odległości 2 m od urządzenia (ISO 3744), z kanałami podłączonymi na wylocie i wlocie powietrza (z wyjątkiem wlotu w wersji z wlotem OD GÓRY).