CHA / K / A / WP 726-P ÷ 24012-P (227 - 762 kW)

CHA / K / A / WP 726-P ÷ 24012-P (227 - 762 kW)

CHA / K / A / WP 726-P ÷ 24012-P (227 - 762 kW)

Ask about product

Product description

CHA / K / A / WP 182-P ÷ 604-P

Aircooled liquid chillers and heat pumps with axial fans for outdoor installation.

 

    • Cooling capacity :    194 - 671 kW
    • Heating capacity :    227 - 762 kW
    • R410A
    • Compressors - scroll
    • Microprocessor control and regulation system
    • Versions :
    •        -  CHA / K / A / WP                    reversible heat pump
             -  CHA / K / A / WP / SSL          super silent reversible heat pump

Ask about product
Rank A

Technical parameters

Reversible  heat pumps CHA/K/A/WP 726-P ÷ 24012-P

Model

Capacity

C/H

Input

power

C/H

Water

flow

Sound

pressure

Dimensions

h x l x p

Transport

weight

Power

supply

[kW] [kW] [l/s] [dB(A)] [mm] [kg] [V/f/Hz]

CHA/K/A/WP 726-P

194

227

68

66

9,27

69 ST

66 SL

58 SSL

2100x2800x2200

1954

400/3/50

CHA/K/A/WP 786-P

217

256

75

75

10,37

67 ST

64 SL

60 SSL

2100x4000x2200

2291

400/3/50

CHA/K/A/WP 826-P

239

272

78

81

11,42

68 ST

65 SL

61 SSL

2100x4000x2200

2409

400/3/50

CHA/K/A/WP 906-P

259

294

85

85

12,37

68 ST

65 SL

61 SSL

2100x4000x2200

2437

400/3/50

CHA/K/A/WP 1048-P

294

342

100

102

14,05

68 ST

65 SL

61 SSL

2100x4000x2200

2567

400/3/50

CHA/K/A/WP 1128-P

322

369

107

106

15,38

69 ST

66 SL

62 SSL

2100x5000x2200

2820

400/3/50

CHA/K/A/WP 1208-P

339

389

113

112

16,20

70 ST

67 SL

62 SSL

2100x5000x2200

2830

400/3/50

CHA/K/A/WP 13010-P

359

420

127

125

17,15

70 ST

67 SL

62 SSL

2100x5000x2200

3019

400/3/50

CHA/K/A/WP 15010-P

421

476

144

141

20,11

73 ST

70 SL

63 SSL

2100x5000x2200

3164

400/3/50

CHA/K/A/WP 16812-P

475

532

162

157

22,69

73 ST

70 SL

64 SSL

2100x6200x2200

3702

400/3/50

CHA/K/A/WP 18012-P

512

566

172

169

24,46 

73 ST

70 SL

65 SSL

2100x6200x2200  3832  400/3/50 

CHA/K/A/WP 21012-P

597

677

207

202

28,52 

73 ST

70 SL

2100x7200x2200   4660  400/3/50 

CHA/K/A/WP 24012-P

671

762

241

226

32,06 

74 ST

71 SL 

2100x7200x2200  4698  400/3/50 

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer .

C-cooling, H-heating, airflow parameters are given for the highest fan speed, cooling/heating capacity is based on the following parameters: cooling water 12°C / 7°C, outdoor temperature: 35°C; heating water 40°C / 45°C, outdoor temperature: 7°C. Sound pressure - ISO 3744.

CERTIFICATES, APPROVALS: PZH

Ask about product

Usage

Chillers designed for installation in medium and large comfort cooling systems and air conditioning industry.

Ask about product