We use cookies to give you the best experience of our website and to provide anonymised, aggregated site usage data.
By closing this message, you consent to our use of cookies on this device in accordance with our cookie policy unless you have disabled them.
Close

MONTAIR WOP

MONTAIR WOP

MONTAIR WOP

Ask about product

Product description

Chilled water units. The Chiller can be watercooled or aircooled, with Free-Cooling technology too. The liquid flow through the unit water coil is managed by a 3-way internal valve. The WOP range features EC Inverter Plug-Fans; high ESP fans are also available as accessory.

The EC Inverter Plug-Fans allow consumptions reduction at partial loads up to 61% comparing to traditional units with radial fans, with the modulation of absorbed power depending on the real thermal load.

The WOP range is available in two air discharge versions:

  • WOPT with top air discharge
  • WOPB with bottom air discharge

WOP can operate at high water temperature (13/18°C) with dedicated HT accessory: coils are optimized for that setpoint to reach an higher energy efficiency.

 


Product characteristic

Cooling capacity from 9 kW to 155 kW.

 

Nomenclature:

  • WOPT... - top air discharge
  • WOPB... - bottom air discharge
  • WOP.../C - cooling only
  • WOP.../E - cooling and heating
  • WOP.../U - cooling and humidification
  • WOP.../D - cooling, heating, humidification and dehumidification
Ask about product

Technical parameters

 

Model

Cooling

capacity

Absorbed

power

 

EER

Acoustic

pressure

T/B

Dimensions

h x l x w

Weight

T/B

Power

supply

- [kW] [kW]   [dB(A)] [mm] [kg] [V/f/Hz]

WOP 0009

8,6 x x 52/46 1980x675x675 188/206 230/1/50

WOP 0013

13,1 x

x

56/51 1980x675x675 192/209 230/1/50

WOP 0018

17,6 x x 59/54 1980x675x675 197/215 400/3/50

WOP 0022

21,7 x x 60/55 1980x675x675 204/221 400/3/50

WOP 0027

27,5 x x 61/56 1980x875x675 241/259 400/3/50

WOP 0031

31,4 x x 61/56 1980x875x675 246/264 400/3/50

WOP 0036

35,9 x x 64/59 1980x1350x890 368/385 400/3/50

WOP 0048

47,7 x x 64/59 1980x1350x890 379/397 400/3/50

WOP 0057

56,6 x x 64/59 1980x1350x890 389/407 400/3/50

WOP 0063

63,4 x x 65/50 1980x1350x890 399/417 400/3/50

WOP 0069

69,3 x x 65/50 1980x1350x890 411/429 400/3/50

WOP 0079

79,1 x x 60/55 1980x1750x890 479/508 400/3/50

WOP 0089

88,9 x x 60/55 1980x1750x890 492/522 400/3/50

WOP 0097

96,8 x

x

61/56 1980x1750x890 508/537 400/3/50

WOP 0104

104 x

x

66/61 1980x2225x890 565/594 400/3/50

WOP 0117

117 x

x

66/61 1980x2225x890 608/637 400/3/50

WOP 0128

128 x

x

66/61 1980x2225x890 626/655 400/3/50

WOP 0142

142 x

x

64/59 1980x2625x890 698/734 400/3/50

WOP 0155

155 x

x

65/60 1980x2625x890 720/755 400/3/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer.

T – top air discharge, B – bottom air discharge

Cooling capacity is based on the following parameters: ambient air temperature 24°C - R.H. 50%, condensing temperature 45°C

CERTIFICATES, APPROVALS: CE, PZH

Ask about product

Usage

  • server assemblies
  • UMTS and GSM power amplifier rooms
  • NOCs
  • computer racks chilling
  • control rooms
  • power supply units
  • areas with extreme heat loads and where constant temperature and humidity parametres are needed
Ask about product