We use cookies to give you the best experience of our website and to provide anonymised, aggregated site usage data.
By closing this message, you consent to our use of cookies on this device in accordance with our cookie policy unless you have disabled them.
Close

MONTAIR TOP

MONTAIR TOP

MONTAIR TOP

Ask about product

Product description

Aircooled direct expansion Dual Fluid units with double circuit: one aircooled direct expansion circuit and one chilled water circuit. The circuits are separated, with non-simultaneous start-up, for back-up operation. The TOP range features EC Inverter Plug-Fans; high ESP fans are also available as accessory.

The EC Inverter Plug-Fans allow consumptions reduction at partial loads up to 61% comparing to radial fans, with the modulation of absorbed power depending on the real thermal load.

The TOP range is available in two air discharge versions:

  • TOPT with top air discharge
  • TOPB with bottom air discharge

The units can operate at high ambient temperature (up to 52°C) with dedicated combination with remote condensers.

 


Product characteristic

Cooling capacity from 26 kW to 118 kW.

 

Nomenclature:

  • TOPT... - top air discharge
  • TOPB... - bottom air discharge

  • TOP.../C - cooling only
  • TOP.../E - cooling and heating

  • TOP.../U - cooling and humidification
  • TOP.../D - cooling, heating, humidification and dehumidification

 

Ask about product

Technical parameters

 

Model

Cooling

capacity

Absorbed

power

 

EER

Acoustic

pressure

T/B

Dimensions

h x l x w

Weight

T/B

Power

supply

- [kW] [kW]   [dB(A)] [mm] [kg] [V/f/Hz]

TOP 1025

25,7 7,0 3,67 61/56 1980x875x675 313/330 400/3+N/50

TOP 1041

41,5 11,4 3,64 63/58 1980x1350x890 505/522 400/3+N/50

TOP 1050

50,3 14,0 3,59 64/59 1980x1350x890 517/534 400/3+N/50

TOP 2066

66,5 17,8 3,73 63/57 1980x1750x890 654/683 400/3+N/50

TOP 2080

80,0 22,7 3,53 66/60 1980x2225x890 811/840 400/3+N/50

TOP 4104

104 28,7 3,63 66/60 1980x2625x890 1017/1052 400/3+N/50

TOP 4118

118 32,5 3,63 66/60 1980x2625x890 1017/1052 400/3+N/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer.

T – top air discharge, B – bottom air discharge

Cooling capacity is based on the following parameters: ambient air temperature 24°C - R.H. 50%, condensing temperature 45°C

CERTIFICATES, APPROVALS: CE, PZH

Ask about product

Usage

  • server assemblies
  • UMTS and GSM power amplifier rooms
  • NOCs
  • computer racks chilling
  • control rooms
  • power supply units
  • areas with extreme heat loads and where constant temperature and humidity parametres are needed