We use cookies to give you the best experience of our website and to provide anonymised, aggregated site usage data.
By closing this message, you consent to our use of cookies on this device in accordance with our cookie policy unless you have disabled them.
Close

MONTAIR XOP

MONTAIR XOP

MONTAIR XOP

Ask about product

Product description

Aircooled direct expansion units. The XOP range features

  • EC Inverter Plug-Fans
  • high ESP fans are also available as accessory
  • The EC Inverter Plug-Fans allow consumption reduction at partial loads up to 61% comparing radial fans, with the modulation of absorbed power depending on the real thermal load
  • available in two air discharge versions: XOPT with top air discharge and XOPB with bottom air discharge.

The units can operate at high ambient temperature (up to 52°C) with dedicated combination with remote condensers.

 


Product characteristic

Cooling capacity from 9 kW to 141 kW.

 

Nomenclature:

  • XOPT... - top air discharge
  • XOPB... - bottom air discharge
  • XOP.../C - cooling only
  • XOP.../E - cooling and heating
  • XOP.../U - cooling and humidification
  • XOP.../D - cooling, heating, humidification and dehumidification
Ask about product

Technical parameters

 

Model

Cooling

capacity

Absorbed

power

 

EER

Acoustic

pressure

T/B

Dimensions

h x l x w

Weight

T/B

Power

supply

- [kW] [kW]   [dB(A)] [mm] [kg] [V/f/Hz]

XOP 1009

9,2 2,4 3,79 53/48 1980x675x675 227/245 230/1/50

XOP 1011

11,5 3,4 3,41 56/51 1980x675x675 236/253 230/1/50

XOP 1015

15,5 4,2 3,70 58/53 1980x675x675 239/257 400/3+N/50

XOP 1020

19,9 5,6 3,55 61/56 1980x675x675 243/260 400/3+N/50

XOP 1025

24,4 6,6 3,69 62/57 1980x875x675 277/295 400/3+N/50

XOP 1030

30,0 8,1 3,73 62/57 1980x875x675 294/311 400/3+N/50

XOP 2035

35,3 10,2 3,47 65/50 1980x1350x890 464/482 400/3+N/50

XOP 1040

40,4 11,3 3,57 65/60 1980x1350x890 460/478 400/3+N/50

XOP 2048

48,2 13,0 3,70 65/60 1980x1350x890 479/497 400/3+N/50

XOP 2055

54,9 14,2 3,86 66/60 1980x1350x890 514/531 400/3+N/50

XOP 2065

65,4 17,4 3,76 64/58 1980x1750x890 599/628 400/3+N/50

XOP 1070

70,2 18,3 3,84 68/62 1980x1750x890 619/648 400/3+N/50

XOP 2080

79,1 21,6 3,67 63/58 1980x1750x890 657/686 400/3+N/50

XOP 2090

90,2 24,6 3,67 67/62 1980x2225x890 743/772 400/3+N/50

XOP 2100

101 28,0 3,61 68/63 1980x2625x890 770/799 400/3+N/50

XOP 4110

111 28,5 3,90 66/61 1980x2625x890 949/984 400/3+N/50

XOP 4120

120 31,5 3,82 67/61 1980x2625x890 975/1011 400/3+N/50

XOP 4130

131 34,7 3,77 67/61 1980x2625x890 973/1009 400/3+N/50

XOP 2140

141 36,7 3,84 71/65 1980x2625x890 998/1034 400/3+N/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer.

T – top air discharge, B – bottom air discharge

Cooling capacity is based on the following parameters: ambient air temperature 24°C - R.H. 50%, condensing temperature 45°C

CERTIFICATES, APPROVALS: CE, PZH

Ask about product

Usage

  • server assemblies
  • UMTS and GSM power amplifier rooms
  • NOCs
  • computer racks chilling
  • control rooms
  • power supply units
  • areas with extreme heat loads and where constant temperature and humidity parametres are needed
Ask about product