We use cookies to give you the best experience of our website and to provide anonymised, aggregated site usage data.
By closing this message, you consent to our use of cookies on this device in accordance with our cookie policy unless you have disabled them.
Close

MONTAIR TIP

MONTAIR TIP

MONTAIR TIP

Ask about product

Product description

High efficiency aircooled direct expansion Dual Fluid units with double circuit: one aircooled direct expansion circuit and one chilled water circuit. The circuits are separated, with non-simultaneous start-up, for back-up operation. The Inverter Scroll compressor and the EC Inverter Plug-Fans vary their delivered power and absorbed power depending on the real requested thermal load. Up to 88% difference between minimum and maximum absorbed power is reachable.

The TIP range features:

  • EC Inverter Plug-Fans;
  • high ESP fans are also available as accessory.
  • electronic expansion valve already included.
  • available in two air discharge versions: TIPT with top air discharge and TIPB with bottom air discharge.

The units can operate at high ambient temperature (up to 52°C) with dedicated combination with remote condensers.

 


Product characteristic

Cooling capacity from 27 kW to 120 kW.

 

Nomenclature:

  • TIPT... - top air discharge
  • TIPB... - bottom air discharge
  • TIP.../C - cooling only
  • TIP.../E - cooling and heating
  • TIP.../U - cooling and humidification
  • TIP.../D - cooling, heating, humidification and dehumidification
Ask about product

Technical parameters

 

Model

Cooling

capacity

Absorbed

power

 

EER

Acoustic

pressure

T/B

Dimensions

h x l x w

Weight

T/B

Power

supply

- [kW] [kW]   [dB(A)] [mm] [kg] [V/f/Hz]

TIP 1026

26,5 8,0 3,44 66/60 1980x975x675 301/329 400/3+N/50

TIP 1048

48,5 14,1 3,45 68/62 1980x1350x890 502/537 400/3+N/50

TIP 2061

61,4 17,1 3,58 69/63 1980x1750x890 644/693 400/3+N/50

TIP 2087

87,5 25,3 3,46 71/65 1980x2225x890 813/867 400/3+N/50

TIP 3120

120 34,5 3,48 73/66 1980x2625x890 1008/1074 400/3+N/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer.

T – top air discharge, B – bottom air discharge

Cooling capacity is based on the following parameters: ambient air temperature 24°C - R.H. 50%, condensing temperature 45°C

CERTIFICATES, APPROVALS: CE, PZH

Ask about product

Usage

  • server assemblies
  • UMTS and GSM power amplifier rooms
  • NOCs
  • computer racks chilling
  • control rooms
  • power supply units
  • areas with extreme heat loads and where constant temperature and humidity parametres are needed
Ask about product