We use cookies to give you the best experience of our website and to provide anonymised, aggregated site usage data.
By closing this message, you consent to our use of cookies on this device in accordance with our cookie policy unless you have disabled them.
Close

CHA / TTY / FC 1301-1 ÷ 5004-2 + FREECOOLING ( 246 - 1443 kW )

CHA / TTY /  FC 1301-1 ÷ 5004-2 + FREECOOLING ( 246 - 1443 kW )

CHA / TTY / FC 1301-1 ÷ 5004-2 + FREECOOLING ( 246 - 1443 kW )

Ask about product

Product description

CHA / TTY /  FC 1301-1 ÷ 5004-2

Water chillers & FREECOOLING technology with axial fans for outdoor installation.

 

  • Cooling capacity :   246 - 1443 kW
  • R134a
  • FREE COOLING
  • Compressors - TURBOCOR
  • Exchanger : plates type
  • Microprocessor control and regulation system
  • Versions :
  •            - CHA / TTY / FC    cooling only

Ask about product

Technical parameters

Water chillers & FREECOOLING CHA/TTY/FC 1301-1÷5004-2.

 

Model

Capacity

cooling

Input

power

cooling

Input

power

free-cooling

Water

flow

evaporator

Sound

pressure

Dimensions

h x l x p

Transport

weight

Power

supply

[kW] [kW] [kW] [l/s] [dB(A)] [mm] [kg] [V/ph/Hz]

CHA/TTY/FC 1301-1

246

71

10,8

12,69

62

2350x4000x2200 3040 400/3/50

CHA/TTY/FC 1401-1

281

80

10,8

14,50

62

2350x4000x2200 3200 400/3/50

CHA/TTY/FC 1701-1

333

94

10,8

17,18

62

2350x5000x2200 3600 400/3/50

CHA/TTY/FC 2201-1

400

116

14,4

20,64

62

2350x5000x2200 3700 400/3/50

CHA/TTY/FC 2601-1

495

146

18

25,54

62

2350x6200x2200 4500 400/3/50

CHA/TTY/FC 3302-1

588

171

21,6

30,34

63

2350x7200x2200 5150 400/3/50

CHA/TTY/FC 4002-1

696

204

21,6

35,91

63

2350x7200x2200 5500 400/3/50

CHA/TTY/FC 4302-1

869

257

25,2

44,84

63

2760x8400x2200 7700 400/3/50

CHA/TTY/FC 4603-1

1046

307

32,4

53,97

63

2760x10050x2200 8800 400/3/50

CHA/TTY/FC 4804-1

1229

357

36

63,42

64

2760x11100x2200 10000 400/3/50

CHA/TTY/FC 5004-1

1443

425

36

74,46

64

2760x11100x2200 10300 400/3/50

CHA/TTY/FC 2602-2

495

143

18

25,54

63

2350x6200x2200 4700 400/3/50

CHA/TTY/FC 3302-2

588

171

21,6

30,34

64

2350x7200x2200 5400 400/3/50

CHA/TTY/FC 4002-2

696

204

21,6

35,91

63

2350x7200x2200 5700 400/3/50

CHA/TTY/FC 4302-2

869

257

25,2

44,84

63

2760x8400x2200 7800 400/3/50

CHA/TTY/FC 4604-2

981

280

32,4

50,62

63

2760x10500x2200 9100 400/3/50

CHA/TTY/FC 4804-2

1229

357

36

63,42

64

2760x11100x2200 10200 400/3/50

CHA/TTY/FC 5004-2

1443

425

36

74,46

64

2760x11100x2200 10500 400/3/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer .

C-cooling, airflow parameters are given for the highest fan speed, cooling/heating capacity is based on the following parameters: cooling water 15°C / 10°C, outdoor temperature: 35°C, freecooling start 15°C; 100 % frecooling outdor temperature 5°C. Sound pressure - ISO 3744.

CERTIFICATES, APPROVALS: PZH

Ask about product

Usage

Chillers designed for installation in medium and large comfort cooling systems and air conditioning industry.

Ask about product