CHA / TTY 1301-1 ÷ 5004-2 series TURBOLINE ( 248 - 1456 kW )

CHA / TTY 1301-1 ÷ 5004-2 series TURBOLINE ( 248 - 1456 kW )

CHA / TTY 1301-1 ÷ 5004-2 series TURBOLINE ( 248 - 1456 kW )

Ask about product

Product description

CHA / TTY 1301-1 ÷ 5004-2

Aircooled liquid chillers with axial fans for outdoor installation.

 

  • Cooling capacity:   248 - 1456 kW
  • EER : 3,35 -3,90
  • R134A
  • Compressors - semihermetic dual TURBOCOR - magnetic levitation centrifuges
  • Microprocessor control and regulation system : TURBOSOFT
  • Versions :
  •      -  CHA / TTY               cooling only
         -  CHA / TTY / MC      cooling only with condenser type Microchannel

Ask about product

Technical parameters

Aircooled liquid chillers CHA/TTY 1301-1÷5004-2

 

Model

Capacity

C

ST

Capacity

C

MC

Input

power

ST

Input

power

MC 

Water

flow

evaporator

Sound

pressure

Dimensions

h x l x p

Transport

weight

Power

supply

[kW] [kW] [kW] [kW] [l/s] [dB(A)] [mm] [kg] [V/ph/Hz]

CHA/TTY 1301-1

248

248

73

64

11,85

62 ST

61 MC

2100x4000x2200

2440 ST

2100 MC

400/3/50

CHA/TTY 1401-1

282

282

81

73

13,47

62 ST

61 MC

2100x4000x2200

2440 ST

2100 MC

400/3/50

CHA/TTY 1701-1

335

335

97

86

 

16,01

62 ST

61 MC

2100x5000x2200

2770 ST

2390 MC

400/3/50

CHA/TTY 2201-1

403

403

 

116

106

19,25

62 ST

61 MC

2100x5000x2200

2790 ST

2415 MC

400/3/50

CHA/TTY 2601-1

509

509

 

150

133

24,32

62 ST

61 MC

2100x6200x2200

3590 ST

3105 MC

400/3/50

CHA/TTY 3302-1

627

627

185

163

 

29,96

63 ST

62 MC

2100x7200x2200

4020 ST

3450 MC

400/3/50

CHA/TTY 4002-1

770

770

221

198

36,79

63 ST

62 MC

2100x7200x2200

4055 ST

3510 MC

400/3/50

CHA/TTY 4302-1

929

929

274

243

44,39

63 ST

62 MC

2500x8400x2200

5710 ST

4940 MC

400/3/50

CHA/TTY 4603-1

1075

1075

311

281

51,36

63 ST

62 MC

2500x10500x2200

6460 ST

5590 MC

400/3/50

CHA/TTY 4804-1

1260

1260

362

328

60,20

64 ST

63 MC

2500x11100x2200

7430 ST

6430 MC

400/3/50

CHA/TTY 5004-1

1456

1456

433

381

69,56

64 ST

63 MC

2500x11100x2200

7640 ST

6810 MC

400/3/50

CHA/TTY 2602-2

509

509

145

132

24,32

63 ST

62 MC

2100x6200x2200

3700 ST

3120 MC

400/3/50

CHA/TTY 3302-2

627

627

185

163

29,96

63 ST

62 MC

2100x7200x2200

4250 ST

3480 MC

400/3/50

CHA/TTY 4002-2

770

770

221

198

36,79

63 ST

62 MC

2100x7200x2200

4270 ST

3695 MC

400/3/50

CHA/TTY 4302-2

929

929

274

243

44,39

63 ST

62 MC

2500x8400x2200

5820 ST

5035 MC

400/3/50

CHA/TTY 4604-2

1075

1075

309

279

51,36

63 ST

62 MC

2500x10500x2200

6690 ST

5785 MC

400/3/50

CHA/TTY 4804-2

1260

1260

362

328

60,20

64 ST

63 MC

2500x11100x2200

7570 ST

6550 MC

400/3/50

CHA/TTY 5004-2

1456

1456

433

381

69,56

64 ST

63 MC

2500x11100x2200

7850 ST

6790 MC

400/3/50

*Technical specifications concern selected models from Klima-Therm offer. Manufacturer continues to improve its products – to confirm the above data please contact the Authorised Dealer .

C-cooling, for the highest fan speed, cooling/heating capacity is based on the following parameters: cooling water 12°C / 7°C, outdoor temperature: 35°C. Sound pressure - ISO 3744.

CERTIFICATES, APPROVALS: PZH

Ask about product

Usage

Chillers designed for installation in medium and large comfort cooling systems and air conditioning industry.

Ask about product