Chillers and water cooled heat pumps, MultiPower series
Chillers and heat pumps are designed for comfort air conditioning and heating systems.
Chillers and heat pumps are designed for comfort air conditioning and heating systems.
Units with the refrigeration system containing R410A (GWP 2088) refrigerant.
Scroll compressor with an oil sight glass. Installed with internal overheating protection and, if required, with a crankcase heater, fitted on rubber vibration dampers.
Units in the cooling/heating version operate using the heat pump function. They can cool or heat water, chilled water or air.
The units in the cooling-only version provide the basic function of cooling water, chilled water or air, while other functions are optional.
Shell and tube heat exchanger with two independent cooling circuits and one water circuit.
Units with the refrigeration system containing R454B (GWP 466) refrigerant.
Units with the refrigeration system containing R452B (GWP 675) refrigerant.
Model
|
EER* COP* |
Capacity C/H |
Absorbed power C/H |
Electric power supply |
Dimensions |
Weight** |
Refrigerant charge Cooling only/ Heat pump |
|
|
kW |
kW |
V/pH/Hz |
mm |
kg |
kg (CO2eq-T) |
CWW/K 726 |
4,25/ 4,25 |
225/ 291 |
53/ 67 |
400/3/50 |
1900/3000/800 |
1370 |
2x18(2x37,584)/ 2x14(2x29,232) |
CWW/K 786 |
4,35/ 4,14 |
248/ 317 |
57/ 74 |
400/3/50 |
1900/3000/800 |
1399 |
2x18(2x37,584)/ 2x14(2x29,232) |
CWW/K 826 |
4,23/ 4,17 |
271/ 345 |
64/ 81 |
400/3/50 |
1900/3000/800 |
1544 |
2x19(2x39,672)/ 2x15(2x31,320) |
CWW/K 906 |
4,19/ 4,16 |
302/ 386 |
72/ 91 |
400/3/50 |
1900/3000/800 |
1554 |
2x19(2x39,672)/ 2x15(2x31,320) |
CWW/K 1048 |
4,34/ 4,15 |
343/ 434 |
79/ 102 |
400/3/50 |
1900/3000/1350 |
1819 |
2x20(2x41,760)/ 2x16(2x33,408) |
CWW/K 1128 |
4,26/ 4,10 |
375/ 474 |
88/ 113 |
400/3/50 |
1900/3000/1350 |
2024 |
2x20(2x41,760)/ 2x19(2x39,672) |
Technical data refer to selected models from the Klima-Therm offer. The manufacturer is constantly improving its products – to verify the data, please contact an Authorized Dealer. C - cooling, H – heating. Cooling capacity- Chilled water from 12 to 7 °C, water temperature at the condenser from 30 to 35 °C.Heating capacity- Heated water from 40 to 45 °C, water temperature at the evaporator from 15 to 10 °C.
* EN14511