Chillers and air cooled heat pumps with screw compressors.
Chillers and heat pumps, operating on R134a refrigerant, are designed for office and industrial air conditioning and heating systems.
Chillers and heat pumps, operating on R134a refrigerant, are designed for office and industrial air conditioning and heating systems.
Units with the refrigeration system containing R134a (GWP 1430) refrigerant.
Semi-hermetic single-screw satellite compressors. With integrated oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, hot gas shut-off valves and stepless capacity control.
Semi-hermetic single-screw satellite compressors. With integrated oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, and hot gas shut-off valves.
Axial fans directly coupled to a three phase electric motor and external rotor, equipped with a grille protecting the fan located at the air outlet.
Units in the cooling/heating version operate using the heat pump function. They can cool or heat water, chilled water or air.
The units in the cooling-only version provide the basic function of cooling water, chilled water or air, while other functions are optional.
Shell and tube heat exchanger with two independent cooling circuits and one water circuit.
Units with the refrigeration system containing R513A (GWP 631) refrigerant.
Agregat
|
EER*
|
Wydajność C/G |
Pobór mocy C/G |
Zasilanie |
Wymiary Tylko chłodzenie/ Pompa ciepła |
Masa Tylko chłodzenie/ Pompa ciepła |
Ładunek czynnika |
|
|
kW |
kW |
V/pH/Hz |
mm |
kg |
kg (CO2eq-T) |
CHA/Y 1202-B |
2,71
|
221 225 |
80 75 |
400/3/50 |
2100/3350/2200 2100/4400/2200 |
2640/ 3080 |
36(51,480) |
CHA/Y 1302-B |
2,93 |
262 255 |
88 78 |
400/3/50 |
2100/3350/2200 2100/4400/2200 |
2730/ 3180 |
38(54,340) |
CHA/Y 1502-B |
2,67 |
302 289 |
112 91 |
400/3/50 |
2100/3350/2200 2100/4400/2200 |
2780/ 3240 |
44(62,920) |
CHA/Y 1702-B |
2,50 |
348 338 |
137 105 |
400/3/50 |
2100/3350/2200 2100/4400/2200 |
2920/ 3400 |
52(74,360) |
CHA/Y 1902-B |
2,48 |
393 390 |
156 120 |
400/3/50 |
2100/4400/2200 2100/5550/2200 |
3120/ 3720 |
64(91,520) |
CHA/Y 2002-B |
2,68 |
453 457 |
167 138 |
400/3/50 |
2100/5550/2200 2100/6700/2200 |
3800/ 4540 |
72(102,960) |
CHA/Y 2602-B |
2,75 |
549 536 |
197 160 |
400/3/50 |
2100/5550/2200 2100/6700/2200 |
4070/ 4720 |
80(114,400) |
CHA/Y 3002-B |
2,91 |
684 662 |
231 191 |
400/3/50 |
2100/6700/2200 2100/7750/2200 |
5270/ 6040 |
110(157,300) |
CHA/Y 3602-B |
2,80 |
806 767 |
284 225 |
400/3/50 |
2100/6700/2200 2100/7750/2200 |
5480/ 6220 |
120(171,600) |
CHA/Y 4202-B |
2,82 |
954 850 |
334 260 |
400/3/50 |
2100/7750/2200 2100/8900/2200 |
6250/ 7060 |
190(271,700) |
CHA/Y 4802-B |
2,67 |
1089 1044 |
402 318 |
400/3/50 |
2100/10050/2200 2100/12250/2200 |
7255/ 8195 |
230(328,900) |
CHA/Y 5402-B |
2,71 |
1218 1172 |
443 350 |
400/3/50 |
2500/10050/2200 2500/12250/2200 |
7715/ 8525 |
280(400,400) |
CHA/Y 6002-B |
2,69 |
1347 1306 |
494 395 |
400/3/50 |
2500/10050/2200 2500/13400/2200 |
8160/ 9180 |
300(429,000) |
CHA/Y 6302-B |
2,74 |
1475 1438 |
531 418 |
400/3/50 |
2500/11100/2200 2500/13400/2200 |
8840/ 9600 |
340(486,200) |
CHA/Y 6802-B |
2,83 --- |
1597 --- |
554 --- |
400/3/50 |
2500/13400/2200 ---/---/--- |
10100/ --- |
400(572,000) |
Dane techniczne dotyczą wybranych modeli z oferty Klima-Therm. Producent stale udoskonala swoje wyroby – aby zweryfikować dane proszę skontaktować się z Autoryzowanym Dealerem. C - chłodzenie, G – grzanie. Nominalna wydajność chłodzenia i grzania wyznaczana jest dla następujących parametrów: tryb chłodzenia temperatura wody chłodzonej 12°/7°C, temperatura powietrza zewnętrznego 35°C; tryb grzania temperatura wody grzewczej 40°/45°C, temperatura powietrza zewnętrznego 7°C,
*EN 14511