Chillers and air cooled heat pumps, AquaPlus series
Chillers and heat pumps from the AquaPlus series, are designed for medium-sized office and industrial air conditioning and heating systems.
Chillers and heat pumps from the AquaPlus series, are designed for medium-sized office and industrial air conditioning and heating systems.
Units with the refrigeration system containing R410A (GWP 2088) refrigerant.
Scroll compressor with an oil sight glass. Installed with internal overheating protection and, if required, with a crankcase heater, fitted on rubber vibration dampers.
The unit is equipped with a circulation pump and a condenser fan regulator which adjusts the unit's capacity to variable loads.
Axial fans directly coupled to a three phase electric motor and external rotor, equipped with a grille protecting the fan located at the air outlet.
Units in the cooling/heating version operate using the heat pump function. They can cool or heat water, chilled water or air.
The units in the cooling-only version provide the basic function of cooling water, chilled water or air, while other functions are optional.
Plate heat exchanger made of AISI 316 stainless steel, soldered, with one cooling circuit and one water circuit or with two independent cooling circuits and one water circuit.
Units with the refrigeration system containing R454B (GWP 466) refrigerant.
Units with the refrigeration system containing R452B (GWP 675) refrigerant.
Model
|
EER* COP* |
Capacity C/H |
Absorbed power C/H |
Electric power supply
|
Dimensions
|
Weight** |
Refrigerant charge |
|
|
kW |
kW |
V/pH/Hz |
mm |
kg |
kg (CO2eq-T) |
CHA/K 182-P |
2,88 3,13 |
47,6 54,1 |
16,1 17,3 |
400/3/50 |
1920/2350/1100 |
595 |
12(25,056) |
CHA/K 202-P |
2,84 3,15 |
54,9 61,8 |
18,7 19,6 |
400/3/50 |
1920/2350/1100 |
624 |
14(29,232) |
CHA/K 242-P |
2,84 3,09 |
63,5 71,4 |
21,8 23,1 |
400/3/50 |
1920/2350/1100 |
663 |
14(29,232) |
CHA/K 262-P |
2,85 3,16 |
72,9 80,3 |
25,0 25,4 |
400/3/50 |
1920/2350/1100 |
682 |
14(29,232) |
CHA/K 302-P |
2,89 3,14 |
83,4 90,4 |
28,2 28,8 |
400/3/50 |
2220/2350/1100 |
791 |
18(37,584) |
CHA/K 363-P |
2,95 3,16 |
95,9 106,0 |
31,4 33,4 |
400/3/50 |
2220/2350/1100 |
918 |
24(50,112) |
CHA/K 393-P |
2,85 3,12 |
110,0 120,0 |
37,4 38,5 |
400/3/50 |
2220/2350/1100 |
927 |
24(50,112) |
CHA/K 453-P |
2,87 3,08 |
127,0 135,0 |
43,3 43,8 |
400/3/50 |
2220/2350/1100 |
1036 |
26(54,288) |
CHA/K 524-P |
2,88 3,06 |
147,0 154,0 |
50,0 50,5 |
400/3/50 |
2220/3550/1100 |
1135 |
28(58,464) |
CHA/K 604-P |
2,99 3,10 |
178,0 187,0 |
58,0 60,4 |
400/3/50 |
2220/3550/1100 |
1374 |
32(66,816) |
Technical data refer to selected models from the Klima-Therm offer. The manufacturer is constantly improving its products – to verify the data, please contact an Authorized Dealer. C - cooling, H – heating. Cooling capacity- Chilled water from 12 to 7 °C, ambient temperature 35°C; Heating capacity- heating water 40°/45°C, ambient temperature 7°C. *EN14511
**for heat pumps, the weight increases by 10%